Electrical permit at 16 Neron Pl
ElectricalFencing
Work description
Background and Code Basis: The existing electrical meter is located in the rear yard of the property, behind a closed fence. Entergy requires unobstructed 24/7 access to all meters. Per NEC 110.26(E)(2), outdoor electrical equipment installations must not be obstructed in a manner that prevents access, and enclosing a meter behind a closed, locked, or latched fence constitutes a code violation as enforced by Louisiana state electrical inspectors. The service disconnecting means must also be at a readily accessible location per NEC 230.70(A)(1). Because the current installation does not comply with these requirements, the meter must be relocated to the front of the property to achieve code compliance and satisfy Entergy’s Customer Installation Standards (CIS).