Building permit at 1830 E BASELINE RD
Work description
Install (2) hood suppression systems. System 1 Ansul consists of (1) 3-gal wet chemical cylinder supporting (2) 1-flow point head in ducts, (2) 1-flow point head in plenum, (1) 1-flow point head over Charboiler, and (3) 2-flow point head over Tilt Skillet. System 2 Range Guard consists of (1) 4-gal wet chemical cylinder and (1) 1.25-gal wet chemical cylinder supporting (2) 1-flow point heads in duct, (2) 1-flow point heads in plenum, (2) 2-flow point heads over the fryers, (1) 1-flow point heads in salamander, and (2) 2-flow point heads over 6-burner range. System also has two manual pull stations, emergency gas/electric shut off valves and is connected to the fire sprinkler monitoring panel. Fusible links rated at 450°F. Signs placed over each hood and manual pull station indicating which hood associates with corresponding manual pull station.
Property history
| Issued | Address | Work description | Est. value | |
|---|---|---|---|---|
| 2026-08-03 | 1830 E BASELINE RD | Modifications to existing ANSUL System for proper coverage of existing tilt skillet in kitchen of an existing indoor amusement building. Adding 1 new 1.5 gallon cylinder, 1 new 3N Remodeling | $3,000 | › |