For two properties: 1209 and 1211 Potomac Street NW, p. management. Since Section 706.8 of the 2017 DCBC refers to Section 705.8.7 (see Exception 1), the required protection shall be provided in the form of physical fire doors, as required by Section 716.5 and referenced in Section 705.8.7.5. Both buildings are fully sprinklered; however, there are significant space constraints. Given the space required to accommodate the multiple door swings associated with each of the required fire doors, as well as the limited occupant loads on each side of the party wall, we respectfully request that a code modification be granted based on our proposed design.